E 5.816.1.1 / 08.16
1
Operation Data
Fluids Oils (mineral oils, synthetic oils, high viscosity oils,
biological oils, phosphate ester)
Water-glycol (cooling uid)
HFC pressure uids
Viscosity AC-LN: 2,000 mm²/s (standard)
ACA-LN / ACAF-LN: see technical data
Temperature range Minimum / maximum ambient temperature:
-20 °C to +40 °C (standard)
Minimum / maximum temperature of the medium: +130 °C
Please contact the technical sales department in the event of
deviating temperatures for applications with water-glycol.
Notice!
Fan switching frequency at max. fan speed (max. volume of air)
must be avoided when operating a cooler at which the temperature
difference between the medium inlet at the cooler and the ambient
temperature can be greater than +50 °C. Quick changes in the
temperature of the cooling element material can lead to a signicant
reduction in service life or to direct damage of the cooling element
due to thermal shock.
Please contact the technical sales department to receive information
about controlled fan drives.
Pressure resistance of the
cooling element
Dynamic operating pressure: 16 bar
Static operating pressure: 21 bar
Fan Axial fan in suction version (standard)
Axial fan in pushing version on request
(note: approx. 10 % less cooling capacity)
Motor Three-phase motor
Efciency class IE2 (only ≥0.75 kW)
Protection class IP55
Insulation class F
Other versions on request.
ErP The fan unit of the AC-LN corresponds to the minimum efciency
levels specied in the Ecodesign directive or ErP directive (Energy-
related Products) 2009/125/EC.
Pump
(only ACA-LN/ACAF-LN)
ACA-LN / ACAF-LN 2-3: screw pump
ACA-LN / ACAF-LN 4-5-6: vane pump
ACA-LN / ACAF-LN 7: screw pump with separate motor
Operating pressure:
max. 10 bar (screw pump)
max. 6 bar (vane pump)
Negative suction pressure of the pump: max. -0.4 bar
Pump motor speed: 3,000 rpm
Noise levels See technical data AC-LN and ACA-LN / ACAF-LN
The noise levels are only reference values as the acoustic properties
of a room, connections and reection have an effect on the noise
level.
Accessories Integrated pressure bypass valve (IBP) or integrated thermal
pressure bypass valve (IBT) (cannot be retrotted, also see options)
Thermostats
Air lter grid or air lter mat
Vibration damper
Air Cooler Industry
AC-LN 1-7 / ACA-LN 2-7 /
ACAF-LN 2-7
General
The AC-LN 1-7 air cooler series can
be used in all areas where either oil or
water-glycol is to be cooled with air.
The coolers with an axial fan can be
used in the return line as well as in the
bypass ow.
The wide range of accessories and
optional versions mean that the coolers
can be adapted exibly to various
applications.
Product Features
The cooler can also be used in the
bypass ow by attaching a pump.
An additional lter enables continuous
ltration of the medium.
l Large product range
l Large cooling performance range
l Modular design
Symbol
E 5.816.1.1 / 08.16
2
1 Drive motor
2 Axial fan
3 Fan housing
4 Heat exchanger
Application Field
Systems with small and medium
cooling requirements, such as:
l Hydraulic systems
l Lubrication systems
l Gears
l Motors
l Generators
l Converters
l Machine tools
Options
Integrated pressure bypass valve
(IBP) / Integrated thermal pressure
bypass valve (IBT)
The bypass channel is integrated in the
cooling element. If a particular pressure
is exceeded, the IBP opens the bypass
channel, thereby protecting the cooling
element from too high a pressure.
Furthermore, the IBT only opens the
cooling element path once a particular
temperature has been reached.
ATEX
The AC-LN (without pump and lter)
is also available for operation in gas
and dust explosive areas. The ATEX
certication applies for a frequency of
50 Hz and 60 Hz.
Marine
The MAR version is for aggressive
ambient conditions, such as industrial
atmospheres, high humidity or high salt
content, which place great demands on
the corrosion resistance and robustness
of the materials used.
Cold Climate / Hot Climate
Use in extreme ambient conditions:
Cold Climate to -40 °C,
Hot Climate to +60 °C
The various versions can also be
combined. Our technical sales
department will be happy to assist
you further.
Design
AC-LN 1
AC-LN 2-3- 4-5-6
1 Axial fan with integrated motor
2 Fan housing
3 Heat exchanger
4 Electrical box
1
2
3
4
1
2
3
4
E 5.816.1.1 / 08.16
3
Design
AC-LN 7
ACA-LN 2-6
1 Drive motor
2 Axial fan
3 Fan housing
4 Heat exchanger
1 Drive motor
2 Low-noise pump*
3 Axial fan
4 Fan housing
5 Heat exchanger
* ACA-LN 2-3 with screw pump
ACA-LN 4-5-6 with vane pump
1
2
3
4
1
2
3
4
5
E 5.816.1.1 / 08.16
4
1 Drive motor
2 Low-noise pump*
3 Axial fan
4 Fan housing
5 Heat exchanger
6 Filter
* ACAF-LN 2-3 with screw pump
ACAF-LN 4-5-6 with vane pump
The lter is equipped with a visual
clogging indicator as standard.
Design
ACA-LN 7
ACAF-LN 2-6
1 Drive motor
2 Axial fan
3 Low-noise screw pump
4 Fan housing
5 Heat exchanger
With external motor-pump assembly
attached onto the base frame.
1
2
3
4
5
5
4
3
1
2
6
E 5.816.1.1 / 08.16
5
Design
ACAF-LN 7
1 Drive motor
2 Axial fan
3 Low-noise screw pump
4 Fan housing
5 Heat exchanger
6 Filter
With external motor-pump assembly attached
onto the base frame. The lter is equipped with
a visual clogging indicator as standard.
1
2
3
4
5
6
E 5.816.1.1 / 08.16
6
Technical Data
AC-LN
Type of cooler
P/N
Fluid [-]
1)
Fluid ow [l/min]
2)
Air ow [m
3
/h]
3)
Fan motor:
Poles / size / ange
Fan motor 50 Hz:
Power / current absorption
[kW / A]
4)
Fan motor 60 Hz:
Power / current absorption
[kW / A]
4)
Noise level
(at 1m distance, 50 Hz) [dB(A)]
Volume [l]
5)
Weight [kg]
6)
kW A kW A
AC-LN1H 3849085 F 120 650 - 0.03 0.23 0.03 0.21 60 0.3 7
AC-LN2S 3860765 F 180 900 4/63/B5 0.18 0.66 0.20 0.75 64 0.7 14
AC-LN2H 3860702 F 180 1,850 2/63/B5 0.25 0.76 0.30 0.76 80 0.7 14
AC-LN3S 3860382 F 180 1,400 4/63/B5 0.18 0.66 0.20 0.75 66 1.0 20
AC-LN3H 3860308 F 180 2,900 2/71/B14 0.55 1.21 0.66 1.50 85 1.0 20
AC-LN4L 3859982 F 200 1,600 6/71/B5 0.25 0.90 0.28 0.80 63 2.3 32
AC-LN4S 3860090 F 200 2,250 4/71/B5 0.37 1.20 0.40 1.10 72 2.3 32
AC-LN5L 3860913 F 250 2,050 6/80/B5 0.37 1.25 0.41 1.15 65 2.8 42
AC-LN5S 3860907 F 250 3,200 4/90/B5 1.10 2.60 1.30 2.20 75 2.8 45
AC-LN6L 3856579 F 250 2,800 6/80/B5 0.37 1.25 0.41 1.15 67 4.6 52
AC-LN6S 3859080 F 250 4,250 4/90/B5 1.10 2.60 1.30 2.20 77 4.6 52
AC-LN7L 3909026 F 300 4,800 6/90/B14 1.10 2.70 1.30 2.70 76 5.2 58
AC-LN7S 3909027 F 300 8,200 4/100/B14 3.00 6.00 3.60 7.20 84 5.2 63
1)
Medium: F = mineral oil or water-glycol, M = mineral oil
2)
Max. ow rate
3)
Air ow data at 50 Hz
4)
AC-LN1: each motor
5)
Fluid in cooling element
6)
Unlled
E 5.816.1.1 / 08.16
7
Technical Data
ACA-LN / ACAF-LN
Type of cooler
Fluid [-]
1)
Fluid ow [l/min]
2)
Air ow [m
3
/h]
2)
Pump displacement [cm
3
/U]
Max. Viscosity [mm
2
/s]
continuous working
3)
Fan motor:
Poles / size / ange
Fan motor 50 Hz:
power / current
absorption [kW / A]
4)
Fan motor 60 Hz:
power / current absorption
[kW / A]
4)
Filter size [-]
Noise level
(at 1m distance, 50 Hz) [dB(A)]
Volume [l]
5)
Weight [kg]
6)
kW A kW A
ACA-LN2S M 13 900 10 500 4/71/B5 0.37 1.20 0.40 1.10 - 64 0.7 21
ACA-LN2H M 27 1,850 10 500 2/80/B5 1.50 3.10 1.80 3.10 - 80 0.7 21
ACAF-LN2S M 13 900 10 500 4/71/B5 0.37 1.20 0.40 1.10 LPF160 64 0.7 22
ACAF-LN2H M 27 1,850 10 500 2/80/B5 1.50 3.10 1.80 3.10 LPF160 80 0.7 22
ACA-LN3S M 36 1,400 28 500 4/90/B5 1.10 2.60 1.30 2.60 - 66 1.0 35
ACA-LN3H M 72 2,700 28 500 2/90/B5 2.20 4.50 2.6 4.5 - 85 1.0 35
ACAF-LN3S M 36 1,400 28 500 4/90/B5 1.10 2.60 1.30 2.60 LPF160 66 1.0 36
ACAF-LN3H M 72 2,700 28 500 2/90/B5 2.20 4.50 2.6 4.5 LPF160 85 1.0 36
ACA-LN4L M 24/34 1,600 28/40 350 6/90/B5 1.10 2.65 1.30 2.25 - 63 2.3 35
ACA-LN4S M 36/52 2,250 28/40 350 4/90/B5 1.80 3.70 2.10 3.60 - 72 2.3 35
ACAF-LN4L M 24/34 1,600 28/40 350 6/90/B5 1.10 2.65 1.30 2.25 LPF160 67 2.3 41
ACAF-LN4S M 36/52 2,250 28/40 350 4/90/B5 1.80 3.70 2.10 3.60 LPF160 72 2.3 41
ACA-LN5L M 24/34 2,050 28/40 350 6/90/B5 1.10 2.65 1.30 2.25 - 65 2.8 45
ACA-LN5S M 36/52 3,200 28/40 350 4/90/B5 1.80 3.70 2.10 3.60 - 75 2.8 45
ACAF-LN5L M 24/34 2,050 28/40 350 6/90/B5 1.10 2.65 1.30 2.25 LPF160 65 2.8 52
ACAF-LN5S M 36/52 3,200 28/40 350 4/90/B5 1.80 3.70 2.10 3.60 LPF160 77 2.8 52
ACA-LN6L M 24/34 2,800 28/40 350 6/90/B5 1.10 2.65 1.30 2.25 - 67 4.6 55
ACA-LN6S M 36/52 4,250 28/40 350 4/90/B5 1.80 3.70 2.10 3.60 - 77 4.6 55
ACAF-LN6L M 24/34 2,800 28/40 350 6/80/B5 1.10 2.65 1.30 2.25 LPF160 67 4.6 62
ACAF-LN6S M 36/52 4,250 28/40 350 4/90/B5 1.80 3.70 2.10 3.60 LPF160 77 4.6 62
ACA-LN7L M 100/150/180 4,800 40/58/69 320/130/240 6/90/B14 1.10 2.70 1.30 2.70 - 76 5.2 74
ACA-LN7S M 100/150/180 8,200 40/58/69 320/130/240 4/100/B14 3.00 6.00 3.60 7.20 - 84 5.2 74
ACAF-LN7L M 100/150/180 4,800 40/58/69 320/130/240 6/90/B14 1.10 2.70 1.30 2.70 LPF280 76 5.2 82
ACAF-LN7S M 100/150/180 8,200 40/58/69 320/130/240 4/100/B14 3.00 6.00 3.60 7.20 LPF280 84 5.2
82
1)
Medium: F = mineral oil or water-glycol, M = mineral oil
2)
Fluid and air ow data at 50 Hz
3)
Depends on pump displacement
4)
For the size 7 the power / current absorption data are those of the fan motor.
For the pump motor on feet refer to the following data:
40/58 cm
3
/U → 3 [kW] / 6.7 [A]
69 cm
3
/U 5.5 [kW] / 10.4 [A]
5)
Fluid in cooling element
6)
Unlled
Cooling in bypass ow: ACA-LN / ACAF-LN
The ACA-LN with integrated boost pump is a complete bypass ow cooling system;
the ACAF-LN is equipped with a high-quality HYDAC lter for additional ltration.
Advantages:
l Stable cooling and ltration (independent of the cycle times of the system)
l Continuous ltration is possible, cooling as required
l Avoidance of pressure surges in the cooling element
l Design of the cooler is in accordance with the cooling capacity required
(not according to the maximum possible return ow volume)
E 5.816.1.1 / 08.16
8
Cooling Capacity and Pressure Difference Δp
Mineral oil
AC-LN / ACA-LN / ACAF-LN
Pressure difference Δp
52
48
44
40
36
32
28
24
20
18
12
8
4
0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340
Oil ow [l/min]
Oil Flow [l/min]
Heat dissipation [kW] at ΔT = 40 °CPressure drop [bar]
Specic heat dissipation [kW/K]
Tolerance: ± 5 %
Measured at 30 mm²/s
Tolerance: ± 5 %
For other viscosities, the pressure loss must be multiplied
by the conversion factor K:
Viscosity (mm²/s) 10 15 22 30 46 68 100 150
Factor K 0.35 0.5 0.75 1 1.4 1.9 2.5 3.5
Cooling capacity:
Dependent on the oil ow rate and the
temperature difference ΔT between oil
inlet and air inlet.
Note:
The values are measured at
ΔT = 40 °C. For smaller ΔT values,
the values can change. You can also
use our cooler calculation software for
designing. Please contact our technical
sales department.
2S-H
3S-H
1H
5L-S
6L-S
7L-S
7S
7L
5S
6S
5L
6L
1H
2S
2H
3S
4S
3H
4L
4L-S
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.0
E 5.816.1.1 / 08.16
9
Cooling Capacity and Pressure Difference Δp
Water-glycol (60/40)
AC-LN
Pressure difference Δp
42
39
36
33
30
27
24
21
18
15
12
9
6
3
0
1,400
1,300
1,200
1,100
1,000
900
800
700
600
500
400
300
200
100
0
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.0
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340
Water-Glycol Flow [l/min]
Water-Glycol Flow [l/min]
Heat dissipation [kW] at ΔT = 30 °C
Pressure drop [mbar]
Specic heat dissipation [kW/K]
Tolerance: ± 5 %
Measured at 2 mm²/s
Tolerance: ± 5 %
6S
Cooling capacity:
Dependant on the water-glycol ow
rate and the temperature difference
ΔT between w/g inlet and air inlet.
Note:
The values are measured at
ΔT = 30 °C. For smaller ΔT values,
the values can change. You can also
use our cooler calculation software for
designing. Please contact our technical
sales department.
7S
7L
6L
5S
1H
2S
3S
2H
3H
5L
4S
4L
1H
2L-S
5L-S
7L-S
6L-S
4S-L
3S-H
E 5.816.1.1 / 08.16
10
Model Type
ACAF-LN 4S - 40 - 1.0 - B - M - A - LPF160 - 10 - 1 - IBT
Cooler type
AC-LN = Air cooler (oil / water-glycol mix)
ACA-LN = Air cooler (oil) with integrated pump
ACAF-LN = Air cooler (oil) with integrated pump and lter
Size / motor speed
1-7 = Size
L = 6 poles (1,000 rpm)
S = 4 poles (1,500 rpm)
H = 2 poles (3,000 rpm)
Displacement cm
3
/rev
10 = Screw pump (ACA-LN / ACAF-LN2)
28 = Screw pump (ACA-LN / ACAF-LN3)
28 = Vane pump (ACA-LN / ACAF-LN4-6)
40 = Vane pump (ACA-LN / ACAF-LN4-6)
40/58/69 = Screw pump (ACA-LN / ACAF-LN 7)
Revision
Clogging indicators (only ACAF-LN)
A = Without clogging indicator
B = With visual indicator (Standard)
D = With electrical and optical indicator
Fluids
F = Mineral oil or water glycol mix (AC-LN)
M = Mineral oil (ACA-LN and ACAF-LN)
Motor voltage
Standard voltages and frequencies for 3 phase motor
A = 230 / 400 V – 50 Hz / 265 / 460 V – 60 Hz
B = 230 / 400 V – 50 Hz
C = 265 / 460 V – 60 Hz
AC-LN1 = 220 - 240 V – 50 / 60 Hz, single phase (Standard)
(tolerance voltage ±10 %)
Other voltages on request.
Size of lter (only ACAF-LN)
LPF160 = ACAF-LN2-6
LPF280 = ACAF-LN7
Filtration rating in micron (only ACAF)
5 = 5 μm Betamicron
®
-4-N (5 BN4HC)
10 = 10 μm Betamicron
®
-4-N (10 BN4HC) (Standard)
20 = 20 μm Betamicron
®
-4-N (20 BN4HC)
Color
1 = RAL 9002 (Standard)
Other colors on request.
Accessories
IBP = Heat exchanger with integrated bypass valve
IBT = Heat exchanger with integrated thermo-bypass valve
AITF = Thermostat (xed)
For all possible accessories, like vibration absorber, air lter grid or
air lter mat please refer to brochure “Accessories for air coolers”.
E 5.816.1.1 / 08.16
11
Dimensions
AC-LN 1
A/2
B
E1
C
D2
D1
D3
E3
Z3
E2
A
Z1 (3x)
PLUG
(4x) Ø F
Air
A/2
AC-LN 2-6
A
±10
B
± 25
C
±10
D1
± 2
D2
± 2
D3
± 2
E1
± 5
E2
± 5
E3
± 5
F
Ø Slot
Z1 Z3
AC-LN1H 355 143 200 255 150 295 288 41 88 9 G3/4" -
AC-LN2H 355 401 330 255 160 295 289 41 58 9 G3/4" -
AC-LN2S 355 396 330 255 160 295 289 41 58 9 G3/4" -
AC-LN3H 455 438 380 255 290 295 388 41 58 9 G3/4" -
AC-LN3S 455 404 380 255 290 295 388 41 58 9 G3/4" -
AC-LN4L 520 517 485 410 425 450 439 51 104 9x20 G1" -
AC-LN4S 520 517 485 410 425 450 439 51 104 9x20 G1" -
AC-LN5L 562 547 542 410 482 450 439 72 94 9x20 G1" -
AC-LN5S 562 563 542 410 482 450 439 72 94 9x20 G1" -
AC-LN6L 640 567 584 410 482 450 497 82 74 9x20 G1 1/4" M22x1.5
AC-LN6S 640 583 584 410 482 450 497 82 74 9x20 G1 1/4" M22x1.5
A/2
B
D3
D1C
D2 E3
E2
E1
A
Z1 (2x)
256 ±10
(4x) Ø F
Air
Air
A/2
E 5.816.1.1 / 08.16
12
AC-LN 7
ACA-LN 2-6
A/2
B
D3
D1
C
D2
C1
E3
E2
E1
A
Z3
Z2 (OUT)
Z1 (IN)
PLUG
(4x) Slot F
Air
A/2
Rotation
A
±10
B
± 25
C
±10
D1
± 2
D2
± 2
D3
± 2
E1
± 5
E2
± 5
E3
± 5
F
Ø Slot
Z1 Z3
AC-LN7L 726 593 706 410 560 450 597 75 74 9x20 G1 1/4" M22x1.5
AC-LN7S 726 613 706 410 560 450 597 75 74 9x20 G1 1/4" M22x1.5
A
±10
B
± 30
C
±10
C1
± 25
D1
± 2
D2
± 2
D3
± 2
E1
± 5
E2
± 5
E3
± 5
F
Ø Slot
Z1
(IN)
Z2
(3x)
Z3
ACA-LN2S 355 567 330 414 370 160 410 289 41 58 9 G 1" G 3/4" -
ACA-LN2H 355 596 330 414 370 160 410 289 41 58 9 G 1" G 3/4"
ACA-LN3S 455 620 380 462 370 290 410 388 41 58 9 G 1" G 3/4" -
ACA-LN3H 455 620 380 462 370 290 410 388 41 58 9 G 1" G 3/4" -
ACA-LN4L 520 697 485 574 410 425 450 439 51 104 9x20 G1 1/4" G1" -
ACA-LN4S 520 699 485 574 410 425 450 439 51 104 9x20 G1 1/4" G1" -
ACA-LN5L 562 707 542 641 410 482 450 439 71.5 94 9x20 G1 1/4" G1" -
ACA-LN5S 562 709 542 641 410 482 450 439 71.5 94 9x20 G1 1/4" G1" -
ACA-LN6L 640 727 584 717 410 482 450 497 81.5 74 9x20 G1 1/4" G1 1/4" M22x1.5
ACA-LN6S 640 729 584 717 410 482 450 497 81.5 74 9x20 G1 1/4" G1 1/4" M22x1.5
A/2
B
E1
C
D2
D1
D3
E3
Z3
E2
A
Z1 (3x)
PLUG
(4x) Slot F
A/2
Air
E 5.816.1.1 / 08.16
13
ACAF-LN 2-6
ACA-LN 7
Z1 (IN)
A/2
B
D3
D1
C
D2
C1
E3
E2
E1
A
Z3
Z2 (OUT)
PLUG
(4x) Slot F
Air
Rotation
A/2
A
±10
B
± 30
C
±10
C1
± 25
D1
± 2
D2
± 2
D3
± 2
E1
± 5
E2
± 5
E3
± 5
F
Ø Slot
Z1
(IN)
Z2
(3x)
Z3
ACA-LN7L 736 593 706 775 560
1)
560 600
1)
600 83 74 9x20 G 2" G1 1/4" M22x1.5
ACA-LN7S 736 607 706 775 560
1)
560 600
1)
600 83 74 9x20 G 2" G1 1/4" M22x1.5
1)
Version with pump displacement 69 [cm³/U]: D1 = 830, D3 = 870
A
±10
B
± 30
C
±10
C1
± 25
D1
± 2
D2
± 2
D3
± 2
E1
± 5
E2
± 5
E3
± 5
F
Ø Slot
Z1
(IN)
Z2
(3x)
Z3
ACAF-LN2S 355 567 330 467 370 160 410 289 41 58 9 G 1" G 3/4" -
ACAF-LN2H 355 596 330 467 370 160 410 289 41 58 9 G 1" G 3/4"
ACAF-LN3S 455 620 380 517 370 290 410 388 41 58 9 G 1" G 3/4" -
ACAF-LN3H 455 596 380 517 370 290 410 388 41 58 9 G 1" G 3/4" -
ACAF-LN4L 520 697 485 619 410 425 450 439 51 104 9x20 G1 1/4" G1" -
ACAF-LN4S 520 699 485 619 410 425 450 439 51 104 9x20 G1 1/4" G1" -
ACAF-LN5L 562 707 542 676 410 482 450 439 71.5 94 9x20 G1 1/4" G1" -
ACAF-LN5S 562 709 542 676 410 482 450 439 71.5 94 9x20 G1 1/4" G1" -
ACAF-LN6L 640 727 584 734 410 482 450 497 81.5 74 9x20 G1 1/4" G1 1/4" M22x1.5
ACAF-LN6S 640 729 584 734 410 482 450 497 81.5 74 9x20 G1 1/4" G1 1/4" M22x1.5
A/2
B
D3
D1
C
D2
C1
E3
E2 E1
A
Z3
Z2 (OUT)
Z1 (IN)
PLUG
(4x) Slot F
Air
A/2
E 5.816.1.1 / 08.16
14
A
±10
B
± 30
C
±10
C1
± 25
D1
± 2
D2
± 2
D3
± 2
E1
± 5
E2
± 5
E3
± 5
F
Ø Slot
Z1
(IN)
Z2
(3x)
Z3
ACAF-LN7L 736 593 706 775 560
1)
560 600
1)
600 83 74 9x20 G 2" G1 1/4" M22x1.5
ACAF-LN7S 736 607 706 775 560
1)
560 600
1)
600 83 74 9x20 G 2" G1 1/4" M22x1.5
1)
Version with pump displacement 69 [cm³/U]: D1 = 830, D3 = 870
ACAF-LN 7
Note
The information in this brochure
relates to the operating conditions
and applications described.
For applications and operating conditions
not described, please contact the
relevant technical department.
Subject to technical modications.
Industriegebiet
66280 Sulzbach/Saar
Germany
Tel.: +49 6897 509-01
Fax: +49 6897 509-454
E-mail: cooling@hydac.com
Internet: www.hydac.com
Via Sceresa, Zona Industriale 3
6805 Mezzovico
Switzerland
Tel.: +41 91 9355-700
Fax: +41 91 9355-701
E-mail: info@hydac.ch
Internet: www.hydac.com
HYDAC COOLING GMBH
HYDAC AG
Mezzovico Branch
Note:
We recommend maintaining a minimum
distance to ensure an unimpeded air
inlet and air outlet. This is half the
height of the cooling element (A/2).
Anything below the minimum distance
can inuence the cooling capacity and
the noise emissions.
A/2
B
D3
D1 C
D2
C1
E3
E2 E1
A
Z3
Z2 (OUT)
PLUG
(4x) Slot F
Air
A/2
Z1 (IN)